17
corresponding wiring board of any one unit, while those for the error indicator and extemal
passive contact switch should be wired to the corresponding wiring board of all units as shown
in the figure below.
7.2 Specification of Power Cord and Air Switch
See the table below for selectin of the power lines and the air switches.
Model
Power Supply
Min. sectional area of the
power cable(mm
2
)
Capability of the
Air Switch Live
(A)
Live
Line
Neutral
Line
Earth
Line
LSQWRF35VM/
NaA-M
380V~415VAC 3Ph
50Hz
6 6 6 32
LSQWRF60VM/
NaA-M
380V~415VAC 3Ph
50Hz
16 16 16 63
A Series Inverter Modular Air-cooled Chiller (Heat Pump)