Service Manual
Change for life
A series modular air-cooled chiller (heat pump)
T1/ R410A /50Hz
T1/ R32 /50Hz

Table of Contents

Other manuals for Gree LSQWRF35VM/NhA-M

Questions and Answers

  • D
    Diane ChavezAug 7, 2025
    What to do if my Gree Heat Pump shuts down due to high pressure?
    • A
      Ashley MooreAug 7, 2025
      If your Gree Heat Pump shuts down due to high pressure protection of the compressor, several factors could be responsible: * Incomplete vacuuming: Re-vacuum the system and recharge refrigerant. * High environmental temperature: Improve ventilation. * Dirty condenser fins: Clean the condenser fins to remove blockages. * Inadequate condensing airflow: Repair the condenser fan. * Failed high-pressure cutoff: Check the high-pressure switch. * Overcharged refrigerant: Check the refrigerant charge and discharge some refrigerant.
  • M
    Michael SimmonsAug 21, 2025
    Why does my Gree Heat Pump compressor motor shut down due to overloading?
    • H
      Howard OrtegaAug 21, 2025
      If your Gree Heat Pump compressor motor shuts down due to overloading, consider these potential causes: 1. Voltage issues: Check that the voltage is no less than 80% and the phase difference does not exceed ±30%. 2. Discharge pressure: Check the discharge pressure to identify the cause. 3. Return water temperature: Check the return water temperature to identify the cause. 4. Faulty overloaded element: Check the compressor current. 5. High environment temperature: Improve ventilation. 6. Phase loss: Check the three-phase resistances. 7. Short-circuited compressor motor.

Summary

1 Product information

1.4 Technical parameters

Detailed specifications including electrical and performance data.

1.4.2 Performance parameters

Performance data like cooling/heating capacity, sound level, and dimensions.

2 Unit control

2.3 Key control logics

Detailed explanations of control logic for various functions and protections.

2.3.8 Protection

Details on recoverable and irrecoverable protection mechanisms.

3 Unit installation

3.2 Preparations before installation

Safety precautions and important considerations before starting installation.

3.2.1 Precautions for installation

Detailed warnings and cautions for safe and proper installation.

3.3 Installation instructions

Step-by-step guide for installing the unit and its components.

3.4 Piping and insulation

Instructions for connecting water pipes and applying insulation.

3.5 Electrical connection

Instructions for wiring the unit, including safety precautions.

3.5.1 Safety precautions

Essential safety measures before and during electrical connections.

3.5.7 Electric wiring diagram

Detailed wiring diagrams for various unit models.

4 Test operation, troubleshooting and maintenance

4.1 Commissioning

Procedures and safety measures for unit commissioning.

4.1.2 Safety precautions for commissioning

Critical safety warnings to follow during commissioning.

4.1.5 Check for initial run

Steps to perform for initial unit run and checks.

4.2 Troubleshooting

Guidance on diagnosing and resolving common unit issues.

4.2.1 Diagnostics

Table of diagnostic names, signal sources, and descriptions of errors.

4.2.2 Flow chart of troubleshooting

Flowcharts for troubleshooting specific protection modes like high pressure.

4.4 Replacement of main parts

Procedures for replacing major components of the unit.

4.4.2 Replacement instructions

Step-by-step guides for replacing specific parts like the compressor.

4.5 Routine maintenance

Procedures for regular maintenance tasks and refrigerant handling.

4.5.1 Repairs to refrigerant leakage

Methods for detecting and repairing refrigerant leaks.

4.7 Maintenance

Requirements for routine and periodic maintenance, including water quality.

4.7.1 Requirements for maintenance

Checklist for routine and periodic maintenance tasks.

Gree LSQWRF35VM/NhA-M Specifications

General IconGeneral
Cooling Capacity35 kW
RefrigerantR410A
Power Supply380-415V/3Ph/50Hz
Noise Level65 dB(A)
Weight450 kg
TypeAir-cooled Scroll Chiller