R
Richard MorganAug 10, 2025
What to do if my Gree Heat Pump shuts down due to high pressure?
- MMatthew DavisAug 10, 2025
If your Gree Heat Pump shuts down due to high pressure protection of the compressor, several factors could be responsible: * Incomplete vacuuming: Re-vacuum the system and recharge refrigerant. * High environmental temperature: Improve ventilation. * Dirty condenser fins: Clean the condenser fins to remove blockages. * Inadequate condensing airflow: Repair the condenser fan. * Failed high-pressure cutoff: Check the high-pressure switch. * Overcharged refrigerant: Check the refrigerant charge and discharge some refrigerant.