10
A Series Inverter Modular Air-cooled Chiller (Heat Pump)
2 Operation range
Please run the unit under the specied operation range as shown in the table below:
■ R32 Series
Item
Water side Air side
Leaving water
temperature (°C)
Water temperature
di󰀨erence (°C)
Ambient DB
temperature (°C)
Cooling 5~20 2.5~6 -15~52
Heating 35~50 2.5~6 -20~40
Maximum and minimum entering water pressures:
Item Minimum entering water pressure Maximum entering water pressure
Cooling
0.06 MPa 1.6 MPa
Heating
3 Outline dimensions
(1) LSQWRF35VM/NhA-M (unit: mm)
Installation hole
1200
729
15
22
765
845
166
146
126 121246
1340
1605
Water oulet:
G1-1/2 male thread
Water inlet:
G1-1/2 male thread
Drain valve