EasyManua.ls Logo

Gree LSQWRF60VM/NhA-M - Control to the Compressor; Control to the Fan; Control to the 4-Way Valve; Control to the Water Pump

Gree LSQWRF60VM/NhA-M
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Unit Control
2.3.3 Control to the compressor
“First on, first off”/ “first off, first on” control indicates the numbered compressor which is started/
stopped rstly will then be stopped/started rstly.
2.3.4 Control to the fan
The fan will start when the unit is turned on and will stop when the compressor is turned off. During
defrosting, the fan does not work but will back to working when defrosting exists.
2.3.5 Control to the 4–way valve
At the cooling mode, the 4–way valve will not work when the unit goes for defrosting or the unit is off.
At the heating mode, the 4–way valve will work when the unit is turned on or defrosting quits.
2.3.6 Control to the water pump
When there is demand for any single unit, the water pump will start. When there is no demand for all
water pumps, the water pump will stop.
2.3.7 Control to the electric expansion valve
The electric expansion valve will be initialized when the controller is powered on for the rst time.
After the compressor has been started, the electric expansion valve starts to adjust its opening angle.
2.3.8 Protection
Recoverable protection
The unit will stop when it receives no signal from the controller. Once there is any communication fault
for any unit, all compressors of this unit will stop and then the water pump will follow.
Irrecoverable protection
(1) Protection against high pressure for the compressor 1/2
When it is detected that the high pressure cutoff of the compressor 1/2 is tripped off, compressor 1/2
will stop immediately. If both compressors are closed, their fans will be delayed to stop. In this case,
the control panel will display an alarm symbol, which should be cleared manually for resuming normal
operation
.
(2) Protection for the ow switch
When it is detected for some unit that the ow switch is opened, this unit will stop. When protection for
the ow switch occurs for all unit, all compressors and water pumps will stop.
(3) Fault of communication
When a single unit does not receive any signal from the controller, this unit will stop automatically. For
the unit with communication fault, when all its compressors stop and then the water pump will follow.
(4) Protection against phase loss/reversal
When there is phase loss or reversal for power supply, power for the main board will be cut off directly.
In this case, there is nothing for the main board.
(5) Protection for abnormal 4–way valve
When it is detected that the entering water temperature is 4°C higher than the leaving water
temperature and the leaving water temperature continuously goes down, the control panel will display this
fault.

Table of Contents

Other manuals for Gree LSQWRF60VM/NhA-M

Related product manuals