Piping size between mode exchanger and downstream indoor unit (“ b
、
c
、
d
、
g”)
Total rated capacity of downsteam
indoor units: X (Btu/h)
Piping size between mode exchanger and downstream indoor unit
Size of connection pipe between indoor branch and indoor unit should be consistent with the
connection pipe of indoor unit.
Piping between indoor branch and indoor unit “e
、
f
、
i
、
j
、
k”
Rated capacity of indoor units
Size of connection pipe between indoor branch and indoor unit
4.2.7.3 Connecting method for indoor unit with capacity of over 48500kBtu/h
When connecting to the indoor unit with capacity of over 48500Btu/h, it is not allowed to connect
with only one branch; it must use two branches controlled by the same mainboard for parallel
connection.
Indoor unit Communication
connection for mode exchanger
Indoor unit No.1 and No.2
Parallel connection can be conducted only as the
combination of this table, it is not allowed to
otherwise connect. Note that after the connection,
manually set the SA2 dial code of corresponding
mainboard, and dial the code in the first place to
number end.
Indoor unit No.3 and No.4
Indoor unit No.5 and No.6
Indoor unit No.7 and No.8