GMV5 HR Heat Recovery Cooling and Heating Mode Exchanger
6
Fig.3.2
Type of wire
Total length of
communication wire between
mode exchanger
and
another indoor/outdoor unit:
L/m(in.)
Wire size
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord
L≤1000(3280-5/6)
AWG16~AWG18
If the wire diameter is enlarged to 2 ×AWG16,
the total communication length can reach
1500m (4921-1/4ft.).
The cord shall be Circular cord (the cores
shall be twisted together).
If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.