Service Manual
Installation and Maintenance
41
1. To realize the function of the air conditioner unit, a special refrigerant circulates in the system. The used refrigerant is the
uoride R32,which is specially cleaned. The refrigerant is ammable and inodorous. Furthermore, it can leads to explosion
under certain conditions. But the ammability of the refrigerant is very low. It can be ignited only by re.
2. Compared to common refrigerants, R32 is a nonpolluting refrigerant with no harm to the ozonosphere. The inuence
upon the greenhouse effect is also lower. R32 has got very good thermodynamic features which lead to a really high energy
efciency. The units therefore need a less lling.
WARNING:
1. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.
Should repair be necessary,contact your nearest authorized Service Centre. Any repairs carried out by unqualied
personnel may be dangerous. The appliance shall be stored in a room without continuously operating ignition sources. (for
example:open ames , an operating gas appliance or an operating electric heater.)
2. Do not pierce or burn.
3. Appliance shall be installed, operated and stored in a room with a oor area larger than 4m
2
.
4. Appliance lled with ammable gas R32. For repairs, strictly follow manufacturer’s instructions only.Be aware that
refrigrants not contain odour.
5. Read specialist’s manual.
Safety Precautions for Refrigerant
Safety Operation of Flammable Refrigerant
Qualication requirement for installation and maintenance man
1. All the work men who are engaging in the refrigeration system should bear the valid certication awarded by the
authoritative organization and the qualication for dealing with the refrigeration system recognized by this industry. If it needs
other technician to maintain and repair the appliance, they should be supervised by the person who bears the qualication for
using the ammable refrigerant.
2. It can only be repaired by the method suggested by the equipment’s manufacturer.
Installation notes
1. The air conditioner is not allowed to use in a room that has running re (such as re source,working coal gas ware,
operating heater).
2. The air conditioner must be installed in a room that is larger than the minimum room area.
The minimum room area is shown on the nameplate or following table.
3. Leak test is a must after installation.
Minimum
room
area( m
2
)
Charge
amount (kg)
≤1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5
oor location / 14.5 16.8 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6
window
mounted
/ 5.2 6.1 7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3
wall
mounted
/ 4 4 4 4 4 4 4 4 4.2 4.6 5 5.5 6
ceiling
mounted
/ 4 4 4 4 4 4 4 4 4 4 4 4 4
Table- Minimum room area (m
2
)
Appliance filled with flammable gas R32.
Before use the appliance,read the owner’s manual first.
Before install the appliance,read the installation manual first.
Before repair the appliance,read the service manual first.
The figures in this manual may be different with the material objects,please refer to the material objects for reference.