G
Gary TaylorJul 29, 2025
What to do if my Greenheck Fire and Smoke Dampers do not fully open or close?
- Jjonathan31Jul 29, 2025
If your Greenheck Fire and Smoke Dampers aren't fully opening or closing, several issues could be the cause. First, the frame may be ‘racked,’ causing the blades to bind. In this case, adjust the frame to be square and plumb. Another potential cause is a loose actuator linkage; if so, close the damper, disconnect the power, and then adjust and tighten the linkage. A defective motor could also be the culprit, requiring replacement. Screws in the damper linkage should be located and removed. If the actuator linkage is hitting a wall or floor, the damper is installed too far into the wall and needs to be moved out to the designated line on the damper label. Finally, contaminants on the damper can impede movement; clean them off using a non-oil-based solvent.