EasyManua.ls Logo

Growatt MIN 4200TL-X - 13 Technical Data; 13.1 Specification

Growatt MIN 4200TL-X
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
13 Technical Data
13.1 Specification
Model
Specifications
2500TL-X
3000TL-X
3600TL-X
4200TL-X
Input data(DC)
Max. recommended PV
power(for module STC)
3500W
4200W
5040W
5880W
Max. DC voltage
500V
Start voltage
100V
Nominal voltage
360V
MPP voltage range
80-500
80-500
80-550
80-550
MPP voltage range at Full
Power
100V-450V
120V-450V
150V-500V
170V-500V
No. of MPP trackers
2
No. of PV strings per MPP
trackers
1
Max. input current per MPP
trackers
12.5A
Max. short-circuit current per
MPP trackers
16A
DC overvoltage category
Category II
Output data(AC)
AC nominal power
2.5kW
3kW
3.6kW
4.2kW
Max. AC apparent power
2.5kVA
3kVA
3.6kVA
4.2kVA
Nominal AC voltage/range*
230/
160~300V
230/
160~300V
230/
160~300V
230/
160~300V
AC grid frequency/range
50-60Hz/44-55Hz;54-65Hz
Max. output current
11.3A
13.6A
16A
19A
Inrush current
<10A
Max output fault current
53A
Max output overload protection
16A
16A
20A
25A
Backfeed current
0A
Power factor(@nominal power)
>0.99
Adjustable power factor
0.8leading… 0.8lagging
THDi
<3%
AC grid connection type
Single phase
AC overvoltage category
Category III
Efficiency

Other manuals for Growatt MIN 4200TL-X