EasyManuals Logo

Growatt MIN 7000TL-X User Manual

Growatt MIN 7000TL-X
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
29
Notice that the connectors are in paired (male and female connectors).
CAUTION
If the inverter is not equipped with a DC switch but this is mandatory in
the country of installation, install an external DC switch.
The following limit values at the DC input of the inverter must not be
exceeded:
Types
Max current
MPPT1
Max current
MPPT2
Max current
MPPT3
7000-8000TL-X(E)
13.5A
27A
-
7000-8000TL-X
13.5A
13.5A
13.5A
9000-10000TL-X
13.5A
13.5A
27A
6.4.2 Connecting the PV Array (DC input)
DANGER
Danger to life due to lethal voltages!
PV array supplies d.c voltage to inverter when exposed to light,before
connecting the PV array, conver some light screens above PV
arrays,ensure that the DC switch and AC breaker are disconnect from
the inverter. NEVER connect or disconnect the DC connectors under
load.
Make sure the maximum open circuit voltage(Voc) of each PV string
is less than the maximum input voltage of the inverter.
Check the design of the PV plant. The Max. open circuit
voltage,which can occur at solar panels temperature of -15, must not

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt MIN 7000TL-X and is the answer not in the manual?

Growatt MIN 7000TL-X Specifications

General IconGeneral
BrandGrowatt
ModelMIN 7000TL-X
CategoryInverter
LanguageEnglish

Related product manuals