Preparation before wiring :
Connect the protective ground wire (PE)
Connect the inverter to the grounding bar through the protective earth (PE) to achieve
grounding protection.
Fig 6.1 Grounding diagram
> Disconnect the inverter DC switch,AC side circuit breaker or switch.
> Measure the voltage and frequency of the public grid (voltage:AC 230V; frequency:50Hz)
>
The recommended specifications of the AC output switch are as follows:
Inverter model
Switch specification
Inverter model
Switch specification
MOD 3000TL3-X
1 0A/230V
MOD 9000TL3-X-AU
20A/230V
MOD 4000TL3-X
1 0A/230V
MOD 1 0KTL3-X
25A/230V
MOD 5000TL3-X
1 5A/230V
MOD 10KTL3-X-AU
25A/230V
MOD 6000TL3-X
1 5A/230V
MOD 11KTL3-X
25A/230V
MOD 7000TL3-X
1 5A/230V
MOD 11 KTL3-X-AU
25A/230V
MOD 7000TL3-X-AU
1 5A/230V
MOD 1 2KTL3-X
25A/230V
MOD 8000TL3-X
20A/230V
MOD 1 3KTL3-X
30A/230V
MOD 8000TL3-X-AU
20A/230V
MOD 1 5KTL3-X
30A/230V
MOD 9000TL3-X
20A/230V
/
/
17
> Good grounding is good for resisting surge voltage impact and im-
proving EMI performance. Therefore,you need to ground the wire before
connecting the AC,DC,and communication cables.
> For a single-machine system,only the PE cable needs to be
grounded;For a multi-machine system,the PE cables of all inverters need
to be connected to the same grounding copper bar to ensure equipoten-
tial connection.