English (GB)
23
2. If the light diode is flashing, the functional module is working 
correctly. The fault may then be in the control panel. See 
section 7.4 Replacing the control panel.
If the status diode of the functional module is off, check if the 
power module supplies voltage by measuring 8.5 VDC on the 
VFE plug connection between the functional module and the 
power module (see fig. 54, J15). If no voltage is measured, the 
connection between the modules or the power module is 
defective.
If the VFE voltage to the functional module is okay, check if the 
voltage between the reference point and the other measuring 
points is okay. The voltage values apply to an operating motor.
Fig. 54 Measuring voltage on the functional module
To measure the voltage listed in the table below, you must use the 
same reference point (ref.) seen on the figure above.
Measure the DC voltage from e.g. "ref." to "1". The measure 
should be between 14.5 V and 15.7 V.
Replace the functional module if the voltage is not correct. See 
section 7.7 Replacing the functional module.
TM06 7718 3816
Use a correctly calibrated measuring instrument.
Pos.
Control voltage [VDC]
Minimum Nominal Maximum
VFE 
(J15)
8.5
1 14.5 15.1 15.7
2 4.8 5 5.2
3 4.8 5 5.2
4 3.2 3.3 3.4
5 23 23.9 24.8
6 4.8 5 5.2
ref. GND