EasyManua.ls Logo

Grundfos PHT A-F250 - Twin System Pressurisation Unit

Grundfos PHT A-F250
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.grundfos.co.uk
GRUNDFOS INSTRUCTIONS
6
5.2 Twin System Pressurisation Unit (PHT A-T models).
A variation of the design allows a single pressurisation unit to provide top-up for two systems,
referred to as a Twin System Pressurisation Unit.
The following schematic shows the arrangement of a twin system pressurisation unit:
Fig. 3 PHT A-T Schematic
This design allows the pressurisation unit to provide top up to two systems independently, with
different parameters, using the same two pumps.
In addition to the features described for a standard pressurisation unit, the following additional
features are provided:
The pressurisation unit is connected into the second system (System 2) through the System 2
Connection (9) via the System 2 Isolation Valve (10), a manual valve provided for isolating the unit
from the system. The System 2 Drain Valve (11) is provided for draining down the unit and/or
system and for commissioning purposes.
The System 2 Pressure Transmitter(AI2) measures the pressure in System 2.
The System 1 Valve (DO3) directs flow from the pumps into System 1.
The System 2 Valve (DO4) directs flow from the pumps into System 2.
When used in twin system mode the Programmable Output 3 (DO8) is set to function as a
critical fault output for System 2 by default and cannot be changed.

Related product manuals