5.1 DIP switches
The PM Rain has a number of settings which can be
made with the DIP switches behind the control panel.
See fig. 6.
Fig. 6 DIP switches
5.2 Enabling the DIP switch settings
When the desired DIP switch settings have been
made, they must be enabled, otherwise the PM Rain
cannot detect the settings.
To enable the DIP switch settings, press [Reset] or
disconnect and reconnect the power supply to the
unit.
TM04 9536 4510
+1.0
+1.0
4 +1.0
5 STOP = START + 1
6 AUTO RESET
ANTI CYCLING
OFF/ON
START
2.5 BAR 1
2
+
+
1.0
0.5
3 +1.0
4 +1.0
5 STOP = START + 1 BAR
6
7 ANTI CYCLING
8
OFF/ON
START
DIP switch
Description Default setting
No. Name
1-4 START
Start pressure (p
start
)
With these DIP switches the start pressure can be set
from 2.5 bar (250 kPa) to 6.0 bar (600 kPa) in steps
of 0.5 bar (50 kPa).
Example:
DIP switch 1 = "ON"
DIP switch 2 = "ON"
Start pressure = 2.5 + 0.5 + 1 = 4 bar
Start pressure = 250 + 50 + 100 = 400 kPa
See section 7.2.1 Starting and stopping conditions.
All set to OFF
p
start
= 2.5 bar
p
start
= 250 kPa
5 STOP = START + 1 BAR
Start/stop with 1 bar (100 kPa) differential
pressure
(This operating mode is only suitable for systems with
a pressure tank).
When the DIP switch has been set to "ON", the pump
stop pressure will be equal to p
start
+ 1 bar (100 kPa).
See section 7.3 Start/stop with 1 bar (100 kPa)
differential pressure.
In systems without a pressure tank, the DIP switch
must be set to "OFF".
OFF
(start/stop according
to water
consumption)
6 AUTO RESET
Automatic resetting of warnings
When the DIP switch has been set to "ON",
the cycling and dry-running warnings will
automatically be reset if they have been activated.
See section 8.2.3 Resetting of dry-running warning.
ON
(manual resetting)
7 ANTI CYCLING
Anti-cycling
When the DIP switch has been set to "ON",
the "Warning" indicator light will illuminate if cycling
occurs. See section 8.1 Anti-cycling.
OFF
8 Not in use