Temperature class
TF110 to CEN 335-2-51.
Liquid temperature
Maximum +110°C.
Continuously: +15°C to +95°C.
Pumps in domestic hot-water systems:
Continuously: +15°C to +60°C.
To avoid condensation in the terminal box and the
stator, the pumped liquid temperature must always
be higher than the ambient temperature. See the
table below:
System pressure
The system pressure is indicated on the pump
flanges:
Inlet pressure
The following minimum pressures must be available
at the pump inlet during operation:
EMC (electromagnetic compatibility)
EN 61800-3.
Sound pressure level
The sound pressure level of the pump is lower than
54 dB(A).
Leakage current
The pump mains filter will cause a discharge current
to earth during operation. I
leakage
< 3.5 mA.
Inputs and outputs
11. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
Ambient
temperature
[°C]
Liquid temperature
Min. [°C] Max. [°C]
15 15 110
20 20 110
25 25 110
30 30 110
35 35 90
40 40 70
Pump type PN 6 PN 10
PN 6/
PN 10
Number
of bolt
holes
UPED 50-120 z 4
UPED 65-120 z 4
UPED 80-120
z 4
z 8
UPED 100-60
z 4
z 8
Pump type
Liquid temperature
75°C 90°C
[bar] [bar]
UPED 50-120 0.4 0.7
UPED 65-120 0.9 1.2
UPED 80-120 1.6 1.9
UPED 100-60 0.95 1.25
Start/stop input External potential-free switch.
Contact load:
5 V, 0.1 mA.
Screened cable.
Loop resistance:
Maximum 130 Ω/km.
Logical levels:
Logical zero: U < 1.5 V.
Logical one: U > 4.0 V.
Max. curve input
Min. curve input
Input for analog
0-10 V signal
External signal: 0-10 VDC.
Maximum load: 1 mA.
Screened cable.
Signal output Internal potential-free change-
over contact.
Maximum load:
250 V, 2 A AC1.
Minimum load: 5 V, 1 mA.
Screened cable.
Bus input Grundfos bus protocol,
GENIbus protocol, RS-485.
Screened cable.
Lead cross section:
0.25 - 1 mm².
Cable length:
Maximum 1200 m.
Subject to alterations.