126
CONTENTS
Page
1. General description 126
1.1 Master pump and slave pump 126
2. Applications 127
2.1 Pumped liquids 127
3. Installation 127
3.1 Terminal box positions 127
3.2 Changing the terminal box position 127
3.3 Changing the nameplate position 128
3.4 Non-return valve 128
3.5 Insulation 128
3.6 Frost protection 128
4. Electrical connection 128
4.1 Supply voltage 128
4.2 Wiring diagram 129
5. Start-up 130
6. Functions 130
6.1 Control of twin-head pumps 130
6.2 Control modes 130
6.3 Selection of control mode 131
6.4 Max. or min. curve duty 132
6.5 Constant curve duty 132
6.6 Temperature influence 133
6.7 Indicator lights 133
6.8 External fault indications 134
6.9 External analog 0-10 V controller 134
6.10 External forced control 135
6.11 Deactivating the control panel 135
6.12 Bus communication 135
6.13 Wireless remote control 135
7. Setting the pump 136
7.1 Factory settings 136
7.2 Control panel 136
7.3 R100 139
7.4 Menu OPERATION 140
7.5 Menu STATUS 140
7.6 Menu INSTALLATION 141
7.7 Priority of settings 143
8. Fault finding chart 143
9. Megging 145
9.1 High-voltage test 145
10. Technical data 145
11. Disposal 146
1. General description
The UPE Series 2000 is a complete range of circula-
tor pumps with integrated differential pressure con-
trol enabling adjustment of pump performance to the
actual system requirements. In many systems, this
will mean a considerable reduction in power con-
sumption, prevent noise from thermostatic valves
and similar fittings, and improve the control of the
system.
The desired head can be set on the pump control
panel.
These instructions apply to the pump types
UPED 50-120, UPED 65-120, UPED 80-120 and
UPED 100-60.
The pump offers the following functions:
Control of twin-head pump:
- Alternating operation,
- Standby operation,
- Synchronous operation,
- Single-pump operation.
Proportional-pressure control (factory setting).
The head is changed in accordance with the flow
demand. The desired head can be set on the
pump control panel.
Constant-pressure control. A constant head is
maintained, irrespective of flow demand. The
desired head can be set on the pump control
panel.
Constant curve duty. The pump runs at a con-
stant speed on or between the max. and min.
curves.
Temperature influence. The head varies depend-
ing on the liquid temperature.
External fault signal via a potential-free output.
External analog control of head or speed from
an external 0-10 V signal transmitter.
External forced control via inputs for:
- Start/stop,
- Max. curve,
- Min. curve (night-time duty).
Bus communication. As the UPE Series 2000
incorporates an input for bus communication, the
pump can be controlled and monitored by a
GRUNDFOS Pump Management System 2000 or
a building management system.
Remote control. The pump can be operated by
means of the Grundfos wireless remote control
R100.
1.1 Master pump and slave pump
Fig. 1
Prior to installation, read these installation
and operating instructions. Installation and
operation must comply with local regula-
tions and accepted codes of good prac-
tice.
TM02 1389 1101
Slave pump
Master pump

Related product manuals