Do not bundle cables in their first 20 m (65.62 ft).
Separate power cords and twisted pair cables at and around the distribution frame.
For ports adjacent to one another on the device, the peer ports on the distribution frame is
preferably not adjacent, for example:
If the device connects to one distribution frame, connect port 1 on the device to port 1 on the
distribution frame and port 2 on the device to port 3 on the distribution frame.
If the device connects to two distribution frames, connect port 1 on the device to port 1 on
distribution frame 1 and port 2 on the device to port 1 on distribution frame 2.
Keep the device and cables away from the interference source, such as a two-way radio and a
high-power variable-frequency drive.