hager
"DALI Gateway C00Cx2" software
Parameters
Seite 128 von 130
Reduced brightness
during pre-warning time
0.1 % … 100 %;
10 %
This parameter determines the reduced
brightness to be adjusted at the time of the
pre-warning.
• The adjustable value is restricted by the
parameterized minimum and maximum
brightness. The standard setting will also
adjust accordingly.
• The reduced brightness will not start the
shutoff function when it reaches or falls
short of the specified shutoff brightness.
• This parameter will be visible only if the
Staircase timer function has been
activated.
Pre-warning time
00:01 … 59:59 [mm:ss]
30 s
This parameter is used for programming
the duration of the pre-warning time. The
pre-warning time is added to the switch-on
time. During the time parameterized at this
point, the reduced brightness will be
adjusted.
• This parameter will be visible only if the
Staircase timer function has been
enabled and the pre-warning time has
been activated.