"DALI Gateway C00Cx2" software
Object table
Seite 23 von 130
4.2.3 Object table
Number of communication objects: 216
Number of addresses (max): 254
Number of assignments (max): 255
Dynamic table management: no
Maximum table length: 255
Objects affecting several channels:
Function: Scenes
Object Function Name Type DP type Flag
208
Extension unit Scenes 1- byte 18.001 C, W, -, (R)
1
Description: 1-byte object for recalling scenes or for storing new scene values.
Function: DALI fault and performance monitoring
Object Function Name Type DP type Flag
210
Feedback DALI error status 1-byte --- C, W, T, (R)
1
2
Description: 1-byte object for transmitting the error status of DALI devices that are connected
individually to the system to the bus. The following bit assignment is used:
Bit 0…5: number of the DALI device (0…63)
Bit 6: lamp error (0 = no error, 1 = error)
Bit 7: electronic ballast error (0 = no error, 1 = error)
Independent of the feedback parameter setting, this object can always receive
telegrams (ValueWrite) as a transmission request. A received telegram will be
immediately answered via this object (ValueWrite) by transmitting the current internal
object status. Bits 0...5 in a request telegram must include the number of the DALI
device. Bits 6 and 7 have to be set to “1”. Otherwise, the request telegram will be
ignored.
1
Each communication object can be read-out. The readout requires the setting of the R flag.
2
Depending on the parameterization the feedback objects are either actively transmitting (T flag) or can be passively read-out (R flag).