hager
"DALI Gateway C00Cx2" software
Scope of functions
Seite 21 von 130
4.2 "DALI Gateway C00Cx2" software
4.2.1 Scope of functions
General:
• Control of a maximum of 64 DALI devices in a max. of 32 groups.
• Manual control of the groups independent of the bus (site operation with broadcast control).
• Feedback of DALI error status or short-circuit and supply voltage failure message.
• Central switching function.
• Incorporation of the groups into up to 16 light-scenes possible.
Channel-oriented:
• Each group features the full scope of functions without any restrictions. All channel-oriented
functions can be parameterized separately for each group. This feature permits independent and
multi-functional control of the DALI devices. However, the Staircase timer function can only be
parameterized for groups 1 ... 16.
• Switching feedback and brightness value: active (after changes or cyclical transmission to the bus)
or passive (object read-out function) feedback function.
• Adjusting the limit values for brightness is possible.
• Dimming response can be parameterized.
• Soft-On or Soft-Off function.
• Disable function or, alternatively, forced-control position function can be parameterized for each
group. With the disable function, blinking of lighting groups is possible.
• Timer functions (ON-delay, OFF-delay, staircase lighting function, also with pre-warning function).
• Response to bus voltage failure and bus voltage return as well as after ETS programming can be
adjusted for each group.
Plug-in:
• Convenient DALI commissioning without additional software components.
• Test function for all created DALI groups or DALI devices: central ON/OFF switching, individual
hardware check (ON / OFF, brightness value preset, device status), individual group check
(switching, dimming) and scene check.
• Export and import of preset parameters in XML format.
• Printing function for creating a configuration report (overview of group assignments or of the entire
device configuration).