RC-2000 Thermostat Installation Instructions
DESCRIPTION
The RC-2000 is a precision digital thermostat designed for 24 VAC heating and cooling systems. The
RC-2000 will support the following systems:
¾ Single Stage Heat/Cool Conventional
¾ Two Stage Conventional (2 Stage Heat / 2 Stage Cool)
¾ Heat Pump (2 Stage Heat / 1 Stage Cool)
¾ Two Speed Heat Pump (3 Stage Heat / 2 Stage Cool)
¾ Dual Fuel Heat Pump
¾ Humidifier and Dehumidifier Control
The RC-2000 has the capability of being controlled both locally and by remote control. It offers
programmability, stand-alone operation, and robust, optically isolated communications with automation
systems, utility control systems, and personal computers.
Electrical rating: 24 V; 2 A; 50/60 Hz
Maximum current: 2 A on any circuit, 3 A total
The following requirements must be observed for installation in Europe: CE
1. This equipment must be installed in accordance with National wiring rules for the country in which it is
installed.
2. All product labels, instructions and markings relating to safety must be translated to a language, which is
acceptable in the country in which this equipment is to be installed.
INSTALLATION
Before installing this thermostat:
1. Read all of the Installation Instructions carefully.
2. Read the Owner's Manual carefully.
3. Ensure that this product is suitable for your application.
4. Ensure that wiring complies with all codes and ordinances.
5. Disconnect power to the control transformer to prevent electrical shock and damage to equipment.
6. Select an appropriate location to ensure an accurate temperature reading.
Document Number 65I00-2 / Rev A / April, 2008
Copyright
¤
2008 Home Automation, Inc.
All Rights Reserved

Questions and Answers

  • R
    Robert HarrellJul 29, 2025
    Why is my HAI RC-2000 Thermostat temperature reading incorrect?
    • S
      Steve ReyesJul 29, 2025
      If your HAI Thermostat displays an incorrect temperature, allow it 30 minutes to adjust. You can also adjust the calibration offset or change the setup option to display Fahrenheit or Celsius.
  • J
    jeffery86Aug 2, 2025
    What to do if heat or cool is inoperative on HAI RC-2000 Thermostat?
    • J
      Joseph RichardsonAug 2, 2025
      If your HAI Thermostat's heat or cool function is inoperative, verify there isn't a break in the W or Y wire. Ensure the minimum off time has passed. Check the system options for correct settings. If the arrow is blinking, wait until the startup delay expires. Ensure the mode isn't set to Off; select Heat, Cool, or Auto. Also, check if a remote system is overriding the thermostat.
  • M
    Mrs. Jacqueline Cochran DDSAug 7, 2025
    How to fix control by remote system not working on HAI Thermostat?
    • A
      Aaron WuAug 7, 2025
      To address a HAI Thermostat that's not being controlled by the remote system, inspect the wires and connections to the section marked “Comm”. Then, check the thermostat address setting, the communications mode setting, and the setup of the remote system.
  • R
    Ryan JonesAug 11, 2025
    What to do if my HAI Thermostat has a display problem?
    • M
      Melissa ClarkAug 11, 2025
      If your HAI Thermostat is displaying a problem, try cycling the power to the thermostat (R).
  • Y
    ypriceAug 15, 2025
    Why is the aux heat on too often on my HAI Thermostat?
    • L
      Luis BryantAug 15, 2025
      If the auxiliary heat on your HAI Thermostat is on too often, it could be due to the heat pump not being able to meet the load because of cold weather, or the thermostat might be in EM Heat mode. In EM Heat mode, only the auxiliary heat is turned on. Try setting the thermostat to Heat or Auto mode.
  • E
    Emily DrakeAug 20, 2025
    Why does my HAI Thermostat heat pump heat in cool mode and cool in heat mode?
    • L
      lwashingtonAug 20, 2025
      If your HAI Thermostat's heat pump heats in cool mode and cools in heat mode, the wires connecting the reversing valve may be reversed. Move the wire from B to O or from O to B.
  • D
    David MooreAug 25, 2025
    How to troubleshoot a dead HAI RC-2000?
    • J
      Joel NelsonAug 25, 2025
      To troubleshoot a dead HAI Thermostat, check the power to the thermostat and review the wiring diagrams.

Summary

INSTALLATION

MOUNTING

TYPICAL WIRING DIAGRAMS

Single Stage Conventional

Single Stage Conventional for Zone Control Systems

Two Stage Conventional (2 Stage Heat; 2 Stage Cool)

Heat Pump (2 Stage Heat; 1 Stage Cool)

Two Speed Heat Pump (3 Stage Heat; 2 Stage Cool)

CONFIGURATION

Settings for two-speed heat pump configuration.

REMOTE SYSTEM WIRING DIAGRAMS

REMOTE SETBACK SWITCH

REMOTE TEMPERATURE SENSOR

SETUP AND CONFIGURATION

INSTALLATION SETTINGS

Configure operating parameters of the thermostat during installation.

System Options

System Type and System Mode

Select thermostat's HVAC system type and operating mode for proper function.

Cool;Heat Min On;Off

Stage Settings

Configure the number of cool and heat stages the HVAC system supports.

EEC Settings

TROUBLESHOOTING TIPS

Thermostat Dead

Actions to take if the thermostat display is blank or unresponsive.

Heat Or Cool Inoperative

Actions to take if the heating or cooling system is not working.

Control By Remote System Not Working

Actions to take if remote system communication is not functioning.

Heat Pump Heats In Cool Mode & Cools In Heat Mode

Actions to take if the heat pump operates in the wrong mode.