Functions and control
Domestic air conditioner
TTC˄ć˅
      Abnormal stop 
    110 
      Decreasing the frequency rapidly˄1HZ/second˅ 
    102 
      Decreasing the frequency slowly (1HZ/10seconds) 
    98 
      The frequency doesn’t change.  
    93 
      Increasing the frequency (1HZ/10second) 
    90 
      Increasing the frequency˄1HZ/1second˅
TTC>=110ć lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the 
indoor, others don’t last. 
7.1.4.2 TC high temperature-preventing control of the indoor heating unit˖
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the 
running state). TC=indoor coil temp.   
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the 
temperature is higher than 55ć, decrease the rotate speed of the compressor and do the high 
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat 
exchanger is lower than 47ć, recover to the normal control.   
          TC(ć)                        The compressor stops                 Fgh_t1  65ć
Fgh_t1ˉ2    
Fgh_t2ˉ2                             N  Decreasing the frequency rapidly     Fgh_t2  59ć
            P  Decreasing the frequency slowly      Fgh_t3   55ć
Fgh_t3ˉ2     
Fgh_t4—2                             Q  Prohibiting increasing the frequency  Fgh_t4   51ć
            R  Increasing slowly                   Fgh_t5   47ć  
Fgh_t5—2                       
Normal 
 N˖Decreasing at the speed of 1HZ/1 second 
     P˖Decreasing at the speed of 1Hz/10 seconds 
     Q˖Continue to keep the last-time instruction cycle 
     R˖Increasing at the speed of 1Hz/10seconds 
Remarks: the outdoor unit 
7.1.4.3 The control of preventing the over current of the compressor: 
During the starting process of the compressor, if the current of the compressor is greater than 11A for 
3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to 
run it only after the power is off. 
During the starting process of the compressor, if the AC current is greater than 8.5A, the frequency of 
the compressor decreases at the speed of 1HZ/second. 
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of 
the compressor decreases at the speed of 0.1HZ/second.   
19