EasyManua.ls Logo

Haier AB12CS1ERA - Page 117

Haier AB12CS1ERA
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Indoor Unit
115
Super Match
Item Model AD18LS1ERA
Function cooling heating
Capacity KW 5.0(1.8~6) 5.5(2~6.2)
Sensible heat ratio 0.73 /
Total power input KW 1.53(0.55~2.1) 1.47(0.6~2.1)
Max. power input W
2100 2100
EER or COP W/W 3.26 3.73
Dehumidifying capacity 10
-
³×m³/h 2.1
Power cable H05RN-F 4G 4.0mm
2
Power source N, V, Hz
1PH, 220-230V~, 50/60Hz
Running /Max.Running current A / A 6.6
2.3-9.5)/9.5 6.6(2.3-9.5)/9.5
Start Current A 3
Indoor
unit
Unit model (color) AD18LS1ERA
Fan
Type × Number CENTRIFUGALX2
Speed(H-M-L) r/min 700/540/400
Fan motor output/ input power W 28/79
Air-ow(H-M-L) m³/h 850/780/600
ESP pa 0/25
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Row 2
Total Area /
Dimension
External(L×W×H) mm×mm×mm 1090/484/220
Package(L×W×H) mm×mm×mm 1174/545/280
Drainage pipe (material , I.D./O.D.) mm
PVC 20/24
Controller
(O-Optional,S-Standard)
Wired YR-E16(O)/YR-E17(S)
Fresh air hole dimension mm NONE
Electricity Heater kW NONE
Sound power Noise level (H-M-L) dB(A) 60
Sound pressure Noise level (H-M-L) dB(A) 43/41/35
Pipe
Liquid Pipe(mm) 6.35
Gas Pipe(mm) 12.7
Connecting Method ared
Weight (Net / Shipping) kg / kg 23/26.5
cooling Pdesignc(kW): 5.0KW SEER/CLASS 5.1/A QCE(Annual electricity consumption for cooling)kWh: 343
heating
Average Pdesignh(-10
o
C) 4.7KW SCOP/CLASS 3.8/A QHE(Annual electricity consumption for heating)kWh: 1702
Warmer Pdesignh(2
o
C) 6.0KW SCOP/CLASS 4.3/A++ QHE(Annual electricity consumption for heating)kWh: 1944
Colder Pdesignh(-22
o
C) / SCOP/CLASS / QHE(Annual electricity consumption for heating)kWh: /
Tdesignh
-10
Tbivalent:-8
o
C TOL:-15
o
C Elbu:0
Max. cooling
condition
Indoor temperature
32
/23
Max. heating condition
Indoor temperature:27
o
C/-
o
C
Outdoor temperature
46
/-
Outdoor temperature:24
o
C/18
o
C
Norminal condition: indoor temperature (cooling): 27
o
CDB/19
o
CWB, indoor temperature (heating): 20
o
CDB
Outdoor temperature(cooling): 35
o
CDB/24
o
CWB, outdoor temperature(heating): 7
o
CDB/6
o
CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level.