Indoor Unit
137
Super Match
Item Model AD48NS1ERA(S)/1U48LS1ERB(S)
Function cooling heating
Capacity kW 12.1(6.0-14.5) 14.1(6.0~16.5)
Sensible heat ratio 0.74
Total power input kW 4.3(2.0---5.8) 4.39(2.0---5.8)
Max. power input W 6000 6000
EER or COP W/W 2.81(C) 3.21(C)
Dehumidifying capacity 10
³×m³/h 5.0
Power cable /
Power source N, V, Hz 3, 380~400, 50
Running /Max.Running current A / A 7.0
2.9-9.5
/9.5 7.0
2.9-9.5
/9.5
Start Current A 5
Indoor
unit
Unit model (color) AD48NS1ERA(S)
Fan
Type × Number CENTRIFUGALX2
Speed(H-M-L) r/min 1260/1190/1110
Fan motor input power kW 0.35
Fan motor output power kW 0.25
Air-ow(H-M-L) m³/h 2090/1970/1792
ESP pa 50/100
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Total area 0.371
Dimension
External
L×W×H
mm×mm×mm 1135×742×270
Package
L×W×H
mm×mm×mm 1357/856/373
Drainage pipe (material , I.D./O.D.) mm PVC 35/39
Controller (O-Optional,S-Standard) Wired YR-E17(S) YR-E16A(O)
Fresh air hole dimension mm 200
Electricity heater kW 0
Sound power Noise level (H-M-L) dB(A) 66
Sound pressure Noise level (H-M-L) 50/48/46
Weight (Net / Shipping) kg / kg 52/55
Piping
Refrigerant
Type / Charge g R410A/2850
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D &O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
DB/19
WB, indoor temperature (heating): 20
DB
Outdoor temperature(cooling): 35
DB/24
WB, outdoor temperature(heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level.