138
Super Match
Item Model AD48HS1ERA(S)/1U48LS1ERB(S)
Function cooling heating
Capacity kW 12.5(6.0-14.5) 14.1(6.0~16.5)
Sensible heat ratio 0.74
Total power input kW 4.4(2.0---6.0) 3.9(2.0---6.0)
Max. power input W 6000 6000
EER or COP W/W 2.84(C) 3.62(A)
Dehumidifying capacity 10
‐
³×m³/h 5.0
Power cable /
Power source N, V, Hz 3N~, 380-400V, 50Hz
Running /Max.Running current A / A 7.0
(
2.9-10.0
)
/10.0 6.8
(
2.9-10.0
)
/10.0
Start Current A 5
Indoor
unit
Unit model (color) AD48HS1ERA(S)
Fan
Type × Number CENTRIFUGALX2
Speed(H-M-L) r/min 1090±30/860±50/690±50
Fan motor input power kW 0.47
Fan motor output power kW 0.27
Air-ow(H-M-L) m³/h 2580/2070/1560(100Pa)
ESP pa 50-150
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Total area m² /
Dimension
External
(
L×W×H
)
mm×mm×mm 1197×830×360
Package
(
L×W×H
)
mm×mm×mm 1378×938×405
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Controller (O-Optional,S-Standard) Wired YR-E17(S) OR YR-E16A(O)
Fresh air hole dimension mm /
Electricity heater kW 0
Sound power Noise level (H-M-L) dB(A) 66
Sound pressure Noise level (H-M-L) 50/46/42
Weight (Net / Shipping) kg / kg 68/75
Piping
Refrigerant
Type / Charge g R410A/2850
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D &O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level.