Indoor Unit
139
Super Match
Item Model AD60HS1ERA(S)/1U60IS1EAB(S)
Function cooling heating
Capacity kW 16.0 17.2
Sensible heat ratio 0.76
Total power input kW 5.29 4.76
Max. power input W 6500 6500
EER or COP W/W 3.02(C) 3.61(A)
Dehumidifying capacity 10
‐
³×m³/h 5.3
Power cable H05RN-F 4G 4.0mm2
Power source N, V, Hz 1, 220~230, 50/60
Running /Max.Running current A / A 8.8/10.5 8.5/10.5
Start Current A /
Indoor unit
Unit model (color) AD60HS1ERA(S)
Fan
Type × Number CENTRIFUGALX2
Speed(H-M-L) r/min 1090±30/860±50/690±50
Fan motor input power kW 0.47
Fan motor output power kW 0.27
Air-ow(H-M-L) m³/h 2580/2070/1560
ESP pa 50~150
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Total area m² /
Dimension
External
(
L×W×H
)
mm×mm×mm 1197×830×350
Package
(
L×W×H
)
mm×mm×mm 1430×940×420
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Controller (O-Optional,S-Standard) Wired YR-E17(S) OR YR-E16A(O)
Fresh air hole dimension mm /
Electricity heater kW 0
Noise level (H-M-L) dB(A) 50/46/42
Weight (Net / Shipping) kg / kg 57/70
Piping
Refrigerant
Type / Charge g R410A/3300
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D &O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level.