EasyManua.ls Logo

Haier AD092MLERA - Page 219

Haier AD092MLERA
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
218
2. Pipe length between outdoors
Gas/liquid pipe: L1+L3 <10m, L2+L3<10m
Oil equalization pipe: L5+L6<10m
Height difference between outdoors: h<5m
Note:
a. HZG-30A includes HZG-20A;
b. The connection pipe among outdoors can't be higher than the outdoor unit check valve to avoid over oil return to
compressor;
c. The piping should be installed horizontal or with slope toward the interior units (less than 15 degree).
Outdoor 1
Outdoor 2 Outdoor 3
h
L5
L1
L2
L3
L4
L6
1st outdoor branch pipe
2nd outdoor branch pipe
Outdoor 1
Min. 200mm
Outdoor 2 Outdoor 3
Outdoor 1 Outdoor 2 Outdoor 3

Other manuals for Haier AD092MLERA

Related product manuals