1. Applicable ambient temperature range:
The machine is adaptive in following situation
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of
T8A/250V(For AD100/125/140/160S2SH5FA,
AD180S2SH5FA/ADH200H1ERG)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H05RN-F 3G 4.0mm2 (outdoor unit 1U71S2SS5FA/1U100S2SN5FA),
or H05RN-F 3G 6.0mm2 (outdoor unit 1U125/140/160/180S2SP5FA),
or H05RN-F 5G 4.0mm2 (outdoor unit 1UH200W1ERK);
The connecting cable should be:
H05RN-F4G 2.5mm
2;
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grounding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.For AD100S2SH5FA,AD125S2SH5FA,AD140S2SH5FA,AD160S2SH5FA,
AD180S2SH5FA,ADH200H1ERG
,
You can
select 10 levels static pressure ,2 level is the factory default static pressure level.For different models, even the static
pressure level is the same; the actual static pressure value is different
static pressure selection need achieved by wired
controller, refer wired controller's manual to get details.Static pressure level selection can also be achieved by the zone
controller,the method refer the zone controller's manual to get details.
5
Safety Precautions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
43/24 C
10/6 C
27 C
15 C
24/18 C
-15 C
40
72
100
120
150
180
210
230
250
300
AD100S2SH5FA
AD125S2SH5FA
AD140S2SH5FA
AD160S2SH5FA
37
50
60
80
100
120
150
170
190
210
Static pressure level ( N)
External static pressure
1
2
3
4
5
6
7
8
9
10
ADH200H1ERG
(pa)
(Factory default)
40
60
100
120
150
180
210
230
250
270
AD180S2SH5FA