11
Item                                                                                     Model AB71S2SG1FA
Function —— Cooling Heating
Capacity W 7100 8000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed (H-M-L) r/min 650/600/550/500
Fan Motor Output/Input 
Power
W 45/50
Air-Flows (H-M-L) m³/h 1260/1070/820/680
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/
¢
7.0
Row —— 2
Total Area m² /
Temp.Scope °C 2.0-7.0
Dimension 
(LxWxH)
External mmxmmxmm 840*840*204
Package mmxmmxmm 990*990*310
Drainage Pipe (Material, I.D/O.D) mm PVC 26/32
Control Type (Remote/Wired)  Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level
(H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 36/33/29/26
Weight (Net/Shipping) kg/kg 27/32
Panel 
(Optional)
Panel Model (Color) PB-950KB
Dimension
External (L*W*H) mmxmmxmm 950/950/50
Package (L*W*H) mmxmmxmm 1000/1000/110
Weight (Net/Shipping) kg/kg 6.5/9
Piping
Refrigerant Type  R32
Pipe
Liquid mm Φ9.52 (3/8)
Gas mm Φ15.88 (5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27
℃
DB/19
℃
WB, indoor temperature (Heating): 20
℃
DB 
Outdoor temperature (Cooling): 35
℃
DB/24
℃
WB, outdoor temperature (Heating): 7
℃
DB/6
℃
WB 
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated 
sound intensity meter.