Cooling Mode Indoor Modication Angle
105
o
C< Discharging Temp.
+50degree/60seconds, it Will Stop Until Up to the Max. Permitted Opening
Angle
98
o
C< Discharging Temp.<=105
o
C Keep the Angle
<=98
o
C 5degree/60seconds, and Reduce to 0 Degree Gradually
Heating Mode Indoor Modication Angle
105
o
C< Discharging Temp.
10degree/60seconds, it Will Stop Until Up to the Max. Permitted Opening
Angle
98
o
C< Discharging Temp.<=105
o
C Keep the angle
<=98
o
C 5degree/60seconds, and Reduce to 0 Degree Gradually
4-way Valve Control in Heating
Unitary: 50s later after compressor start up, the 4-way valve start to operate. When compressor stops or unit is not
in heating mode, the 4-way valve is closed after compressor stop for 2 minutes and 55s.
compressor ON
OFF
4-way valve ON
OFF
50 S(E)
2 minutes and 55s
Electric Heater Control
If compressor has not run for a long time, the refrigerant will deposit on the bottom of compressor and mix with the
refrigeranr oil. When re-startup, because low pressure reduces, refrigerant will be segregated from the refrigerant
oil and cause soam in the oil, which will make compressor exhaust a lot of oil. Therefore please stop heating the
compressor bottom to ensure the low pressure in startup period should not go down greatly.
• Ambient temp. TA≤32degree, when compressor stops, the electric heater will be electried.
• When TA≥32degree, or compressor running, the electric heater will be off.
Heater ON
OFF
Ambient temp. TA(℃) 27 32
Multi: Protection when 4-way valve can not reverse in heating: 15 minutes later after compressor startup, if
indoor coil average temp. is below 5degree and keeps for 1 minute, the unit will stop and occur the 4-way valve
protection.
compressor ON
OFF
4-way valve ON
OFF
50 S(E)
2 minutes and 55s