Quit condition of oil return:
1 minute later after oil return is over
& Td‐Tcm>30℃
OR OR Ts‐Tc>30℃
Tc<‐35℃
Max. 10 minutes
Oil return procedure in heating mode:
Quit condition of oil return
Max. 9 minutes(E)
OR OR Td‐Tcm<20℃ for 30s(5 minutes later, begin to count)
&
T s ‐Tc<15℃ for 30 S(5 minutes later, begin to count)
Running for min. 5 minutes(E)
Send oil return signal oil return beginning oil return over
Inverter compressor indicated FQY 60s oil return frequency 120s
Soft startup
0HZ
0HZ
5s
outdoor motor auto auto
auto(TC control)
4-way valve ON
OFF
15s
450pulse 450 pulse
300pulse (E)
PMV auto open angel auto open angle
all indoor motor ON
OFF anti-freeze startup
Quit condition of oil return:
Oil return procedure in heating mode:
Quit condition of oil return
OR
OR
OR
OR
Max.9 minutes (E)
Max.10 minutes
Running for min.5 (E)
1 minutes later after oil return is over
Td-Tcm
<
20°C for 30s (5 minutes later, begin to count)
Td-Tcm
>
30°C
Ts- Tc
<
15°C for 30s (5 minutes later, begin to count)
Ts- Tc
>
30°C
Ts- Tc
<
-35°C
&
&