Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
26
Installation of indoor unit
Selection of installation place
Place where it is easy to route drainage pipe and outdoor piping.
Place away from heat source and with less direct sunlight.
Place where cool and warm air could be delivered evenly to every corner of the room.
Place near power supply socket. Leave enough space around the unit (refer to installation
drawings).
Fixing of the unit
Position of the wall hole
Wall hole should be decided according to installtion place and piping direction. (refer
to installation drawings)
Making a wall hole
Drill a hole of 70mm dia. with a little slope towards outside.
Install piping hole cover and seal it with putty after installation.
1.
2.
Fixing of indoor unit
To prevent it from fall off, please fix the unit with fall-prevention fitting at wall and L-
shaped metal at floor.
INDOOR
OUTDOOR UNIT
wall hole
wall thinkness
( Cross section of wall hole )
70mm
Self-tapping
screw
all-prevention fitting metal (accessory)
Wood screw
L-shaped metal
(accessory)
Please install the whole unit
horizontally,with a slop of 1
degree at front and rear,left
and right.
Installation of fall-prevention fitting metal:
Fix the fitting metal to the wall by screws so that there is no clearance between them.
With the unit set up vertically, fix the fitting metal to the unit with screws while making an adjustment
at the long portion of the hole so that there is no clearance between the upper surface and the
fitting metal.