Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
84
Equivalent length=actual length+(0.2×curling quantity)
b. Correction factor due to the height drop between I.U&O.U
If in cooling mode, the outdoor unit is lower, while in heating mode, the outdoor unit is upper, only in
this case, in addition that the above correction factor due to the piping length is taken into
consideration, the following factor should also be taken into consideration:
Height drop 5m 10m 15m 20m 25m 30m
Correction factor 0.01 0.02 0.03 0.04 0.05 0.06
c. Correction factor due to the air flow
High speed: 1.0; Med speed: 0.95; Low speed: 0.9