Seivice diagnosis

Domestic air conditioner

11.4.6 Over-current of the compressor
Electrify the machine again and turn it on
with the remote controller, If malfunctions
are reported before or upon the compresso
r
being started up,
IPM Module is damaged and
needs replacing.
Repair the power supply
the system may have been over or under charged
with gas, which can be judged through the
pressure of the measuring system.
YES
NO
YES
NO
The compressor is started normally, but
malfunctions are reported after it has
run for some time. Check the powe
r
supply is too low or too high
NO
Method of
malfunction detection
Malfunction detection
conditions
Troubleshooting
he current of the compressor is too high
when the IPM Module is damaged or the compressor is damaged. power supply
voltage is too low or too high
Supposed causes
LED1 flash 3 or 24 or 25 times
Outdoor diplay
Ŷ
Faulty IPM Module
Ŷ
Faulty compressor
Ŷ
Faulty power supply
* Caution
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred..
.
54

Other manuals for Haier AS07BS4HRA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier AS07BS4HRA and is the answer not in the manual?

Haier AS07BS4HRA Specifications

General IconGeneral
BrandHaier
ModelAS07BS4HRA
CategoryAir Conditioner
LanguageEnglish

Related product manuals