AS24GS1/2ERA 1U24GS1ERA-SM Service Diagnosis
Domestic Air Conditioner
68
7.3.4 The IPM and outdoor PCB don’t communicate or Related Abnormality
(G,B((-/BC.L4EJ/// / LED1 flash 4 times
Indoor Display
F3
/
/
/
8*,A(B/(K/
/ / / / / /
Communication is detected by checking the IPM module and the outdoor PCB
8E4KG)+,C()/// / ///
=*,*+,C()
8E4KG)+,C()/
/ / / / /
Ƶ
/ /
The outdoor PCB broken leads to communication fault
/
=*+C.C()/
/ / / / / / / /
Ƶ
/ /
The IPM module broken leads to communication fault
/
"()BC,C()./

&GLL(.*B/
Ƶ
The outdoor PCB is broken
/
"EG.*./
Ƶ
The IPM module is broken
Ƶ
Communication wiring disconnected
P-(GM4*.A((,C)D /
X/"EG,C()
/
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
NO
YES
Are they good?
1) Pull out and reinsert the terminals.
2) Replace connected wire
1) Check whether Terminal CN23 and CN22 on the outdoor
mainboard CN10 and CN11 on IPM module
2) Check whether the connected wire between IPM and outdoor
YES
Replace the outdoor IPM
module with a new one.
Replace the outdoor mainboard with a new one
Electrify the machine again and
turn it on, Check whether the
voltage between 1 and 2 o
f
Terminal CN22is about DC5V,
Check whether the voltage
between2 and 3 of Terminal
CN22 is about DC15V,
NO