Functions and control
17 Domestic air conditioner
7.1.4 Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or changed to
non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the four-way valve.
7.1.5 Protection function
7.1.5.1 TTC high temperature-preventing protection
Once the machine is started, it can run TTC(air-blowing temp) overheating protection of air-blowing,
but air-blowing sensor malfunction must alarm after 4 minutes during which the compressor is started
(during the course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for eac
h time: continuously sampling for 8 times, then order them and take the mean
value of the middle
2 values), take the mean value.
TTC(℃)
Abnormal stop
108
Decreasing the frequency rapidly1HZ/second
104
Decreasing the frequency slowly (1HZ/10seconds)
102
The frequency doesn’t change.
100
Increasing the frequency (1HZ/10second)
93
Increasing the frequency1HZ/1second
TTC>=110
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
7.1.5.2 TC high temperature-preventing control of the indoor heating unit
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the running