EasyManuals Logo

Haier AS25THMHRA-C User Manual

Haier AS25THMHRA-C
537 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #385 background imageLoading...
Page #385 background image
Service diagnosis
43 Domestic air conditioner
10.3.11 Loss of synchronism detection
Inverter side current detection is abnormal
Outdoor Display
LED1 flash 18 times
LED1 flash 19 times
Method of The position of the compressor rotor can not detected normally
Malfunction
Detection
Malfun
ction when the wiring of compressor is wrong or the connection is poor;
Decision or the compressor is damaged
Conditions
Supposed
Faulty The wiring of compressor
Causes
Faulty compressor
Faulty PCB
T
roubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or parts
damag
e may be occurred.
Within 3 minutes af
ter the machine is
supplied with power and turned on with
the remote controller, check whethe
r
the compressor can start up
1. The wiring of compressor is incorrect
or the connection
is poor;
2.
The compressor is damaged
At first, the compressor start up ,soon the
compressor stopped with the LED1 on the
outdoor PCB blinks1Hz19/18 times
IPM Module is damaged and needs
replacing.
the Malfunctions exist also, the
compressor is damaged replace a
new one
YES
NO
YES
Malfunction unsolved
Maybe there is some disturbance

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier AS25THMHRA-C and is the answer not in the manual?

Haier AS25THMHRA-C Specifications

General IconGeneral
BrandHaier
ModelAS25THMHRA-C
CategoryAir Conditioner
LanguageEnglish

Related product manuals