Functions and control
18 Domestic air conditioner
TC() The compressor stops Fgh_t1 63
Fgh_t12
Fgh_t22 N Decreasing the frequency rapidly Fgh_t2 59
P Decreasing the frequency slowly Fgh_t3 56
Fgh_t32
Fgh_t4—2 Q Prohibiting increasing the frequency Fgh_t4 53
R Increasing slowly Fgh_t5 40
Fgh_t5—2
Normal
NDecreasing at the speed of 1HZ/1 second
PDecreasing at the speed of 1Hz/10 seconds
QContinue to keep the last-time instruction cycle
RIncreasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
7.1.5.3 The control of preventing the over current of the compressor:
During the starting process of the compressor, if the current of the compressor is greater than 17A
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the power is off.
During the starting process of the compressor, if the AC current is greater than 15A, the frequency
of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 14A, the frequency
of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A, the frequency
of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 12A the frequency of
the compressor increase
s at the speed of no faster than 0.1HZ/second.
7.1.5.4 The protection function of AC current:
During the starting process of the compressor, if the
AC current is greater than 17.5Afor 3 seconds,
stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20
minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only
after the the power is off.
During the starting process of the compressor, if the AC current is greater than 15A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 14A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A, the frequency of
the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 12A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, theres compensation for AC current protection.