EasyManua.ls Logo

Haier AV08IMVEVA - System Status Display and Control; E2 Control Parameters Display and Setting

Haier AV08IMVEVA
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
SW1 SW2 SW3 function Digital tube LD1 ~ 4 display
Outdoor
unit
address
0-3
14
(
E
)
15
(
F
)
Frequency converter INV1 module temperature Unit: degree
15
(
F
)
15
(
F
)
Frequency converter INV2 module temperature Unit: degree
③
System status display and control (host)
④
E2 control parameters display and setting
SW1 SW2 SW3 function Digital tube LD1 ~ 4 display
0 0 2 Refrigerant type 410A represents 410A refrigerant
0 1 2
The same outdoor unit total
number and total capacity
LD1
:
The total number of outdoor unit
LD2
:
Display “-”
LD3/ LD4
:
Total outdoor unit capacity (unit: Horse)
For example: 3-48 said 3 outdoor machines, with a total
capacity of 48 horses
0 2 2 Total indoor unit capacity 50 represents 50 horses
0 3 2
The indoor units within the
same system
For example: 64
0 4 2
Number of indoor unit
working
Temperature sensor ON as a sign of the work of the indoor
unit
0 5 2
With the outdoor unit running
mode the same indoor unit
number
For example: 13
0 6 2 Cooling target temperature
Unit: degree
0 7 2 Heating target temperature
0 8 2
Automatic recovery of
refrigerant
Note: the end of the recovery
must be canceled or reset
When the outdoor stops, press START (SW5) for 2 seconds,
display 1111, start. (the outdoor is set to work in a state of
operation)
Press STOP (SW6) for 2 seconds, display 0000, stop
0 10
(
A
)
2
Test run setup
Note: the end of the test run
must be canceled or reset
When the outdoor stops, press START (SW5) for 2 seconds,
display 1111, start. (the outdoor is set to work in a state of
operation)
Press STOP (SW6) for 2 seconds, display 0000, stop
0 11
(
B
)
2 Outdoor unit mode 0-normal C-only cool H-only heat
0 12
(
C
)
2
Indoor unit expansion valve
fully open
Press START (SW5) for 2 seconds, display 1111, indoor
valve fully open 2 minutes, 2 minutes after the automatic
shutdown valve
0 13
(
D
)
2 All the indoor unit for cooling
Press START (SW5) for 2 seconds, display 1111, fully open
;
Press STOP (SW6) for 2 seconds, 0000, closed
0 14
(
E
)
2 All the indoor unit for heating
0 15
(
F
)
2
Cancel all manual control
(running class)
Press START (SW5) for 2 seconds, display 1111 cancel; or
press STOP (SW6) for 2 seconds, display 0000, cancel
Remove all manual control (part), closed indoor unit
Each need to be set, setting method:
(1)Press START (SW5) for 2 seconds, display 1111, enter the set state, ashing display the current value
(2)According to UP (SW4) or DOWN (SW7) adjustment parameters
(3)After the adjustment is completed
<A> In the current state of the code, effectively set the time by pressing STOP (SW6) for 2 seconds, showing 0000,
keeping the current settings and exit the set state, stop ashing display, waiting for 2 minutes after the power off and then
re power up
<B> The current set time is not set by STOP (SW6) or change the dial selection, do not save the current set value, exit
the set state, stop ashing display
<C> Effective time setting: the machine with the contract number and set off a low temperature automatic operation
function for 10 minutes, the other for 30 seconds.
Electric wiring and the application