44
Function Parameter Range Default
Zone 1 Compensation Temp. of Cooling -15~15°C 0°C
Zone 1 Compensation Temp. of Heating -15~15°C 0°C
Zone 2 Compensation Temp. of Cooling -15~15°C 0°C
Zone 2 Compensation Temp. of Heating -15~15°C 0°C
DHW Compensation Temp. -15~15°C 0°C
Swimming Pool Compensation Temp. -15~15°C 0°C
Note: Actual target temperature of system=Set target temperature of controller + Compensation temperature
③
System installation
Tap “SYSTEM INSTALLATION” icon in Picture 22 to enter the system control parameters setting interface. You can set
the operating parameters for the system.
Picture 25
Function Parameter Range Default
Control Mode of Zone1 Main controller, Third party controller, IDU ambient Temp. sensor Main controller
Control Mode of Zone2 Main controller, Third party controller, IDU ambient Temp. sensor Main controller
Control Mode of DHW Main Controller, Third Party Controller Main Controller
Control Mode of Pool Main Controller, Third Party Controller Main Controller
Zones Water Temp. Control Mode Direct, Auto curve, Set curve Direct
Auxiliary Heat Source IDU Electric Heater, Boiler, IDU Electric Heater + Boiler
IDU electric
Heating
Outdoor Temp. for (Heat to Cool) 0~30°C 15°C
Outdoor Temp. for (Cool to Heat) 0~30°C 10°C
DHW On Temp. 30~55°C 45°C
Ambient Temp. of Heating Off 5~35°C 27°C
△
T for Heating On 0~15°C 6°C
Outdoor Temp. for Heater On -20~15°C 0°C
Heater On Delay Time 0~120min 60min
Heater On
△
T of Target Temp. -10~-2°C -3°C
Heater Off
△
T of Target Temp. -8~0°C -1°C
Tank Re-heat Temp. -12~2°C -3°C
△
T for Cooling On 1~15°C 5°C
Target Temp. of DHW IO Board 25~75°C 45°C
Target Temp. of Pool IO Board 20~30°C 24°C
Travel Time of Mixing Valve 30s~90s 60s
Operation instructions for controller