Maintenance
Fault Code
-1represents the A system ,-2 represents the B system
S/N
Fault code
Fault description
Remarks
1
E1
Fault in air-condition flow switch
One lock
2
E5
-1/2/3/4
Compressor module three-phase AC input phase
sequence mission protection
4 times in 60min,
locked.
3
E6
Three-phase AC input phase sequence error protection
One lock
4
E7
Fault in return water temperature sensor
recoverable
5
E8
Fault in outlet water temperature sensor
recoverable
6
E9
Fault in outdoor ambient temperature sensor
recoverable
7
E15
Fault in communication of wired controller
recoverable
8
E16
Fault in communication of main board
recoverable
9
E48-1/2/3/4
Fault in overcurrent protection of system fan
One lock
E49-1/2/3/4
High-pressure protection of system
3 times in 60min,
locked.
10
E51-1/2/3/4
Over-current protection of system compressor
3 times in 60min,
locked.
11
E52-1/2/3/4
Open circuit or short circuit in exhaust temperature
sensor of system compressor
recoverable
12
E53-1/2/3/4
Open circuit or short circuit in coil (outlet) temperature
sensor 1 of system
recoverable
13
E54-1/2/3/4
Open circuit in low-pressure sensor of system
recoverable
14
E55
-1/2/3/4
Low pressure protection of system
3 times in 60min,
locked.
15
E56-1/2/3/4
Open circuit or short circuit in suction temperature
sensor of system
recoverable
16
E58-1/2/3/4
Over temperature of exhaust temperature sensor of
system compressor
3 times in 60min,
locked.
17
E59-1/2/3/4
Over temperature of coil (outlet) temperature sensor
1/2 of system
recoverable
18
E60-1/2/3/4
Open circuit or short circuit in coil (outlet) temperature
sensor 2 of system
recoverable
19
E64
Overload protection of system pump in air conditioning
side
One lock
20
E65
Overload protection of system eletrical assisted heater
in air conditioning side
One lock
21
E68
Overtop or low protection of outdoor ambient
temperature
recoverable
22
E69-1/2/3/4
Refrigerant lack protection of system
One lock
23
E71
Overtop Temperature difference of in and out water
3 times in 60min,
locked.
24
E72
Running time exceeded
One lock
25
E218
One lock
26
-1/2/3/4
Fault in EE of main board
Note:
1 The 60 minutes time of the accumulated three times within 60 minutes is calculated with natural time;
2
The flicker of the fault lamp is related to its corresponding number except that E72 does not flicker.
3
After 4 minutes of communication between the wired controller and the unit, it still displays "in
communication, please wait a moment..." The reason may be for multiple units to dial the code set to the
host.
After troubleshooting,recover after press the "+" and "-" combination keys of the line controller for 5
seconds or power failure of the unit.
4
,-3represents the C system ,-4 represents
the D system