5. Installation 
ENGLISH SECTION D
High ESP Duct Product Information
The High ESP Duct Indoor Air Handler ships consisting of a 
single assembly. The High ESP Duct indoor unit is operated 
via a factory supplied wired remote control.  
that are located at all four corners of the High ESP Duct
The High ESP  Duct unit receives  230 volt line  voltage 
from  a  connection  at  the  outdoor  condensing  unit. 
There  is  no  requirement  for  independent  line  voltage 
connections. 
The High ESP Duct unit has a built-in condensate pump and 
Duct unit. This hose connects the High ESP Duct 
condensate drain outlet to the building’s condensate 
drain system. 
Included with the High ESP Duct unit is factory provided 
insulating tape. This tape should be placed over the 
refrigerant piping connections at the indoor unit to prevent 
sweating.  
Built-in 
Condensate
Pump and 
Float Switch
Indoor AM24LP2VHA AM36LP2VHA AM48LP2VHA
Rated Cooling Capacity Btu/hr 24,000 35,000 47,000
Rated Heating Capacity Btu/hr 26,500 37,500 52,000
Voltage, Cycle, Phase V/Hz/-
208/230/60/1 208/230/60/1 208/230/60/1
Fan Speed Stages 4+Auto 4+Auto 4+Auto
Airflow (Turbo/ High/
Med/Low/Quiet) CFM
845/670/530/470 1100/950/735/675
1350/1150/930/765
Motor Speed (Turbo/ High/
Med/Low/Quiet) RPM
950/860/760/700
1000/920/860/810 1180/1080/1010/960
Max. External Static Pressure in.W.G 
(Pa)
0.6(150) 0.6(150) 0.6(150)
Indoor Sound Level dB (Turbo/High/
Med/Low)
38/35/32/29 32/28/25/23
41/36/33/31
Dimension: Height in (mm)
9 7/8 (250) 9 7/8 (250) 9 7/8 (250)
Dimension: Width in (mm)
37 5/8 (957) 59 (1500) 59 (1500)
Dimension: Depth in (mm)
25 3/4 (655) 28 3/8 (720) 28 3/8 (720)
Weight (Ship/Net)- lbs (kg)
81.1/68.8(36.8/31.2) 130.1/121.3 (59/55) 132.3/114.6 (60/52)
Connections Flare Flare Flare
Liquid O.D. in 3/8 3/8 3/8
Suction O.D. in 5/8 5/8 5/8
Drainpipe Size O.D. in  1 1/4 1 1/4 1 1/4
Internal Condensate Pump
Standard
Standard Standard
Max. Drain-Lift height in(mm)
27 9/16(700) 27 9/16(700)
27 9/16 (700)
Introduction - Overview
YR-E17 Wired Controller
See Section E for more information
assembly.
High ESP
The High ESP Duct unit will install above the ceiling or in a soffit