Unclog pipe and 
water pump
Is drain pan dirty and 
float switch ineffective?
Is pump motor in good condition?
Is drain pipe clogged?
yes
Check if float switch is in good 
condition with multimeter
Are indoor sensors for ambient 
temperature and coil properly located?
Is resistance of indoor sensor correct?
Does four-way valve work properly?
Relocate
Replace four-way valve
Is outdoor four-way valve in good 
condition during heating cycle?
Does small relay coil 
of four-way valve have 
a voltage of 12V DC?
no
Relay is broken. 
Replace PCB
Is indoor unit malfunction caused by lack of refrigerant?
charge refrigerant
Is heat exchange effect adversely affected 
by heavy dust in indoor and outdoor units?
cleaning
10) Temperature cutoff protection
confirm the malfunction 
according to the fault code list
yes
yes
no
yes
no
yes
no
yes
no
yes
no
Replace sensor
yes
Replace indoor PCB
11) Fault in drain system
confirm the malfunction 
according to the fault code list
no
yes
Replace water pump
yes
yes
Clean drain pan
no
Is float switch holder tinted that float 
can't move, or too close to pump 
motor that interference arises?
yes
Adjust holder
no
yes
Replace float 
switch
no
Replace indoor PCB
Note: Float switch is close in normal state, when being activated, it is open. Voltage between both ends is 0V 
5V when open.
when close, approximately
Troubleshooting