For 
remote 
type, flash 
times 
Failure 
code on 
wired 
controller 
For central 
control, 
failure code 
Failure description  Reason 
10  08  21  Drainage system failure  Float switch broken down for more than 
25m continuously 
1  01  01  Indoor ambient temp. sensor 
failure 
sensor broken down or short circuit for 
more than 2m continuously 
2  02  02  Indoor coil temp. sensor failure sensor broken down or short circuit for 
more than 2m continuously 
3  4A  11  Outdoor ambient temp. sensor 
failure 
sensor broken down or short circuit for 
more than 2m continuously 
4  49  12  Outdoor coil temp. sensor 
failure (compressor 
discharging temp. sensor) 
Sensor broken down or short circuit for 
more than 2m continuously 
5  48  10  Over-current protection    CT check abnormal 3 times in 30m 
6  53  14  High pressure abnormal  High pressure switch acts 3 times in 30m 
8 07 06  Communication between wired 
controller and indoor abnormal
Communication abnormal for more than 
4m continuously 
9 06 05  Communication between 
indoor and outdoor abnormal 
Communication abnormal for more than 
4m continuously 
11  0B  30  Outside alarm signal input  Outside signal broken down for more than 
10s 
12 03 20  Gas pipe temp. sensor 
abnormal 
Sensor broken down or short circuit for 
more than 2m continuously 
13  0D  31  Solenoid valve abnormal  Solenoid valve act incorrectly 3 times 
continuously 
15  05  17  EEPROM abnormal  EEPROM data missing 
16 54 26D  Outdoor pressure switch or 
discharging protector abnormal
Pressure switch or discharging protector 
disconnected; or CN11 on indoor PCB 
disconnected. The failure occurs only 
when there is no outdoor PCB. 
1.1 For convertible type units
1. Failure code
Failure code