Failure 
code on 
wired 
controller 
Power lamp 
flash 
times/LED on 
PCB flash times 
failure description  Reasons 
E0  10  Fault in drain system    Float switch is open   
E1 1 
Indoor ambient temp. sensor 
failure 
Sensor broken down or short circuit for more than 
2m continuously 
E2 2 
Indoor pipe temp. sensor failure Sensor broken down or short circuit for more than 
2m continuously 
E3 3 
Outdoor ambient temp. sensor 
failure 
Sensor broken down or short circuit for more than 
2m continuously 
E4 4 
Outdoor pipe or discharge 
temp. sensor failure 
Sensor broken down or short circuit for more than 
2m continuously or outdoor discharge temp. over 
120℃  for 3 times continuously in 30m   
E5 5 
overcurrent   Indicate phase failure when been electrified for 
the first time, indicate overcurrent protection 
during working procedure   
6  High pressure malfunction  Outdoor high pressure switch acts   
E6 
16 
Low pressure 
malfunction 
Outdoor low pressure switch acts or the 
proctector on the top of compressor breaks for 
protection  
E8 8 
Communication failure between 
indoor PCB and panel or wired 
controller  
communication abnormal for more than 4m 
continuously 
E9 9 
Communication failure between 
indoor and outdoor unit 
communication between indoor PCB and outdoor 
PCB open for more than 4m   
E7 13 
Temperature cutoff protection  System  failure. System cooling or heating 
function abnormal 