EasyManuals Logo

Haier HBU-42CH03 User Manual

Haier HBU-42CH03
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #247 background imageLoading...
Page #247 background image
3) High pressure protection
Confirm the fault according
to the fault code list
yes
Check and reconnect
no
Are connectors of pressure switch in good condition?
Is high side pressure switch
activated? (If not, DC voltage is 0V.)
yes
Replace PCB
no
Is the high side pressure detected by the
gage higher than threshold value? The
threshold value is indicated on the switch
yes
Replace high pressure switch
no
yes
if outdoor stop valves of gas pipe
and liquid pipe are open totally
Open the valves
no
Is indoor filter or heat exchanger dirty?
Cleaning
yes
yes
Repair fan motor or fan capacitor
no
no
Repair pipe
yes
Is piping twisted or deformed?
yes
Does indoor fan work properly during
cooling cycle? Does outdoor fan work
properly during heating cycle?
no
Check if system is overfed according
to equalized pressure in halt.
yes
Evacuate and recharge
no
Is reading of discharging pressure gage oscillatory?
no
Bad operation codition, such as ultra low
outdoor temperature
yes
There is air in system. Evacuate and recharge
-247-
Troubleshooting

Other manuals for Haier HBU-42CH03

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier HBU-42CH03 and is the answer not in the manual?

Haier HBU-42CH03 Specifications

General IconGeneral
BrandHaier
ModelHBU-42CH03
CategoryAir Conditioner
LanguageEnglish

Related product manuals