and medium of wind volume when it is under heating mode. 
Modification index table for set temperature 
Mode 
Content of modification  Modified variable  Modified parameter 
Operation mode modi hp 
fication 
ETBL0   
 operation modification
ETBL1   
Weak wind volume 
modification 
ETBL2   
Heating 
Medium wind volume 
modification 
ETBL3   
Operation mode modification  ETBL4   Cooling & 
moisture 
removing 
 operation modification
ETBL5   
2.4 temperature level control   
2.4.1 Deviation   
Work out the deviation of temperature level as follows: 
In heating mode: E=(Remote-control set temperature+ modified value)-room 
temperature 
In cooling & moisture removing mode: E= room temperature -(Remote-control set 
temperature + modified value) 
2.4.2 Compressor OFF 
  E is minus and |E|>ΔT 
  Heating  Cooling 
ΔT 
TCHAHL
  TCHACL   
afterΔT changes 
TCHAHH
  TCHACH   
condition forΔT changes 
 
The compressor stops after 120 seconds of continuous detection 
When the operation starts,according to the table above, the unit  will operate 
according to the after-the-ΔT-change parameters before the compressor stops 
for the first time. 
From the time the compressor stops to the time it starts again, the operation will 
follow the  ΔT (except the moisture  removing mode) 
When the operation starts and the operation modes change (except when the idle 
mode is over) and  the deviation is bigger than –ΔT, the compressor starts. 
When the compressor is working and the remote-controller set temperature falls 
below –ΔT, the compressor stops. 
2.4.3 Compressor operation 
When the compressor is kept idle for 3 minutes, the deviation E will be higher 
than  -△T+0.67℃ and the compressor will start working. 
2.4.4 DASH operation   
When the operation starts or the operation mode changes (except when the 
compressor is switched on after being off), the compressor is on and the indicated 
maximum frequency should be as follows: 
 
Models:
HSU-12HS03/R2(DB)
HSU-09HS03/R2(DB)Domestic Air Conditioner