Timer on, Timer off and sleep control are available. 
2.3 Dehumidifying mode: (Tr: inlet air temperature,Ts:the set temperature) 
The background lighting of the LCD is aquamarine blue 
Temperature control range : 16℃—30℃ 
Temperature control precision: ±1℃ 
control character: 
  When Tr (indoor temperature) > Ts (temperature setting) +2℃, compressor and 
outdoor fan motor run continuosly with indoor fan motor runnig in accordance with 
the wind speed setting. 
  When Tr ranges from Ts to Ts +2℃, outdoor fan motor and compressor are on for 
10 minutes and off for 6 minutes, the indoor fan motor is off in 3 minutes after 
shutdown of compressor and gives breeze in other time. 
  When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor 
fan motor enter breeze mode 3 minutes later after shut down of compressor. 
  When all the ranges alternate, there is  ±1℃ difference.  
Wind speed control: 
    Automation: When Tr >= Ts + 5℃, the wind speed is high. 
      When Ts+3℃≤ Tr <Ts+5℃, the wind speed is medium. 
    When Ts+2℃≤ Tr <Ts+3℃, the wind speed is low. 
    When Ts≤ Tr <Ts+2℃, the machine gives breeze intermittently. 
When Tr < Ts, the indoor fan motor is shut off. in 3 minutes 
When Tr < Ts, the machine gives breeze after 3 minutes 
Manual operation: When the temperation sensor is off or the Indoor fan motor runs 
intermittently, the indoor fan motor can not be operated by hand (compelling 
automatic operation), along with the indoor fan motor can be operated in cooling 
mode. While controlling fan motor by hand in cooling mode, the cooling ranges 
include wind speed setting and refriferation range, others are the same as fan motor in 
automation mode. 
compressor control:The compressor can’t be controlled by temperature sensor in 2 
minutes after   
startup and also can’t be started again at least 3 minutes later after shutdown. There 
are 3-minutes protection with power on for the first time (over 3 minutes with 
power off). The compressor must be started again 3 minutes later after shutdown. 
There is no 2-minutes limit when changing the temperature setting or shutting off the 
machine  
through the remote controller, and the machine can be shut down immediately. 
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor 
startup. 
Controlling the position of air door: set the position of air door as required. 
Protection of frost is available (disable in test run or heating mode): In order to prevent the 
indoor heat   
exchanger from freezing (in refrigation or dehumidifying mode), the compressor 
will be shut off    when the temperature of the indoor coil pipe is or below 0℃ and 
the  compressor runs for  over 5 minutes. When the temperature of the indoor 
Air Conditioner