coil pipe ascends to over 7℃, the compressor is restarted (must meet a 3-minutes 
delay) 
Timer on, Timer off and sleep control are available. 
2.4 Heating    mode: (Tr: inlet air temperature,Ts:the set temperature) 
The background lighting of the LCD is red 
Temperature control range : 16℃—30℃ 
Temperature control precision: ±1℃ 
Control Character: 
   When Tr ≤ Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan 
motor runs as in cold blast avoidance mode, and 4℃of compensation is added after 
compressor is started. 
   When Tr>Ts+5℃, compressor is off, and the indoor fan motor runs as in cold blast 
avoidance mode. 
   When Tr<Ts+5℃, compressor, four-ways valve and outdoor fan motor is on, and the 
indoor fan motor runs as in the mode of avoiding cold blast. 
Control of indoor fan motor: 
Manual operation: The wind speed can be set to high, medium, low or automatic as 
required. 
Automatic operation: When Tr < Ts, the wind speed is high; 
        When Ts=<Tr<Ts+2℃, the wind speed is medium. 
        When Tr>= Ts+2℃, the wind speed is low. 
Control of air door: setting the position of air door as required. 
compressor control:The compressor can’t be controlled by temperature sensor in 2 
minutes after startup and also can’t be started again at least 3 minutes later after 
shutdown. There are 3-minute protection with power on for the first time (over 3 
minutes with power off). The compressor must be started again 3 minutes later after 
shutdown. 
There is no 2-minutes limit when changing the temperature setting or shutting off the 
machine through the remote controller, and the machine can be shut down 
immediately. 
Avoiding electrical shock: outlet air is available 2 seconds later after startup. 
Timer on, Timer off and sleep control are available. 
Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts 
runnig 10 seconds earlier than compressor does. After compressor stops runnig, the 
4-way valve continues running for 2 minutes and 30 seconds then stops. If changing 
the unit from heating to cooling, the 4-way valve is shut off 2 minutes later and 
compressor is started 3 minutes later. 
Cold blast avoidance mode: 
      (1)Compressor is interrupted during the defrosting operation and continues to run after 
defrosting is completed. When the indoor exchanging temperature is below 23℃, 
the indoor fan motor is off. When the indoor exchanging temperature is above 23℃, 
the indoor fan motor is running at weak speed. 
   (2)If the temperature of coil pipe can’t be above 38℃  4 minutes later after startup, fan 
motor is running at the preset wind speed. 